2x 0(4)..20mA input transmitter 0(4)..20mA input transmitter Voltage input transmitter
-Input: dual (0)4..20mA
-Totally isolated and polarity
insensible inputs
-Linearity better then 0.05%FS
-Output: Modbus RTU server on
RS485 Schneider polarization
-fact.prg. address:0xDC (220),
re-programmable
-fact.prg.baudrate:9600,8,N,1
-Mounts on Type T DIN-rail
-12V to 24V DC power, 70mA
-Input: (0)4..20mA, isolated and
polarity insensible
-Linearity better then 0.05%FS
-24V 50mA aux.supply, isolated
-Output: Modbus RTU server on
RS485 Schneider polarization
-fact.prg. address:0xDC (220),
re-programmable
-fact.prg.baudrate:9600,8,N,1
-Mounts on Type T DIN-rail
-12V to 24V DC power, 70mA
-Input: in range of 0-10Vdc
isolated,1kVdc
-Linearity better then 0.05%FS
-Output: Modbus RTU server on
RS485 Schneider polarization
-fact.prg. address:0xDC (220),
re-programmable
-fact.prg.baudrate:9600,8,N,1
-Mounts on Type T DIN-rail
-12V to 24V DC power, 70mA
CODE:D22-2x420-485-ISO CODE:D22-420-485 CODE:D22-U-485
PWM input transmitter Pulse counter& transmitter Quadrature counter& transmitter
-Input: Pulse Width Modulated
signal, max.ampl.:-12V..+12V
min.ampl.:0/5V, max.10kHz
-Accepts NPN/OC type sources
-Output: Modbus RTU server on
RS485 Schneider polarization
-fact.prg. address:0xDC (220),
re-programmable
-fact.prg.baudrate:9600,8,N,1
-Output isolated from DC power
-Mounts on Type T DIN-rail
-12V or 24V DC power, 70mA
-Input: rectangular pulse signal
5%..95%,max.ampl.:-12V..+12V
min. ampl.:0V/5V, max.10kHz
-Accepts NPN/OC type sources
-Counter capacity:4x10^9
-Output: Modbus RTU server on
RS485 Schneider polarization
-fact.prg. address:0xDC (220),
re-programmable
-fact.prg.baudrate:9600,8,N,1
-Output isolated from DC power
-Mounts on Type T DIN-rail
-12V or 24V DC power, 70mA
-Input: quadrature-encoded
pulses, duty 45%..55%,
max.ampl.:-12V..+12V(0..24V)
min.ampl.:0V/5V, max.10kHz
-Direct or reverse counting
-Counter capacity:+/-2x10^9
-Output: Modbus RTU server on
RS485 Schneider polarization
-fact.prg. address:0xDC (220),
re-programmable
-fact.prg.baudrate:9600,8,N,1
-Output isolated from DC power
-Mounts on Type T DIN-rail
-12V or 24V DC power, 70mA
CODE:D22-PWM-485-12(24) CODE:D22-CNT-485-12(24) CODE:D22-QCNT-485-12(24)
Thermocouple input transmitter RTD input transmitter Strain gage signal input transmitter
-Input: K* type thermocouple
-Range:0-52.4mV(0-1300grdC)
-Cold junction compensated
-Linearized cf.ITS-90
-Linearity better then 0.1%FS
-Isolated from DC power,1kVdc
-Output: Modbus RTU server on
RS485 Schneider polarization
-fact.prg. address:0xDC (220),
re-programmable
-fact.prg.baudrate:9600,8,N,1
-Mounts on Type T DIN-rail
-12V to 24V DC power, 70mA
-Input: RTD, Pt100 or Pt1000
-Range:-20..+450grdC
-Linearized cf.IEC751 Class B
-Linearity better then 0.02%FS
-Isolated from DC power,1kVdc
-Output: Modbus RTU server on
RS485 Schneider polarization
-fact.prg. address:0xDC (220),
re-programmable
-fact.prg.baudrate:9600,8,N,1
-Mounts on Type T DIN-rail
-12V to 24V DC power, 70mA
-Input: differential voltage from
resistive bridge type sources
-Fixed gain instrumentation
amplifier with high CMRR
-Bridge supply voltage:+5Vdc
-Input isolated from DC power
-Output: Modbus RTU server on
RS485 Schneider polarization
-fact.prg. address:0xDC (220),
re-programmable
-fact.prg.baudrate:9600,8,N,1
-Mounts on Type T DIN-rail
-12V to 24V DC power, 70mA
CODE:D22-TCK-485 CODE:D22-RTD-485 CODE:D22-GAGE-485-x: Gain:1,2,5,10,20,50,100,500,1000
MEISHI.422 input transmitter Four contact state input transmitter AC/DC V/I input transmitter
  -connects to and reads data
from a MEISHI.422 type sensor
-Output: Modbus RTU server on
RS485 Schneider polarization
-fact.prg. address:0xDC (220),
re-programmable
-fact.prg.baudrate:9600,8,N,1
-Linearity better then 0.1%FS
-Isolated from DC power,1kVdc
-Mounts on Type T DIN-rail
-12V or 24V DC power, 70mA
-Inputs : 8V...28V voltage levels
with common return, isolated
from output and power
-Output: Modbus RTU server on
RS485 Schneider polarization
-fact.prg. address:0xDC (220),
re-programmable
-fact.prg.baudrate:9600,8,N,1
-Mounts on Type T DIN-rail
-12V to 24V DC power, 70mA
-Input V: 90-250Vrms, 50Hz
-Input I: 0-14Arms
-True RMS and power factor
measurement
-All inputs isolated, 1kVdc
-Output: Modbus RTU server on
RS485 Schneider polarization
-fact.prg. address:0xDC (220),
re-programmable
-fact.prg.baudrate:9600,8,N,1
-Linearity better then 1%FS
-Mounts on Type T DIN-rail
-12V to 24V DC power, 70mA
CODE:D22-M422-485 CODE:D22-4C-485 CODE:D22-UI-AC-485-12(24)
Parametrii fizico-constructivi
 
Dimensiuni in mm
Constructie modulara semideschisa cu montare pe sina DIN 35mm (DIN EN 50022) prin mechanism de zavorire elastica.
Material carcasa: nylon V0
Greutate max.50g
Clasa de protectie IP20
RoHS: Conform cu RoHS
REACH: Nu contine substante listate SVHC
DEEE: contine materiale reciclabile

 

Price list
  Item     1-5     6-30    over 30   Availability
 Signal-to-RS485
  D22-2x420-485-ISO      21          *          *         2 weeks   
  D22-420-485      19       *          *      in stock
  D22-U-485      19       *             *     in stock
  D22-PWM-485      23       *          *      in stock
  D22-CNT-485      23       *          *      in stock
  D22-QCNT-485      23       *           *     in stock
  D22-TCK-485      32           *           *         in stock   
  D22-RTD-485      32       *           *      in stock
  D22-GAGE-485-x      32       *              *     in stock
  D22-M422-485       *       *           *          **
  D22-4C-485      17       *           *      in stock
  D22-UI-AC-485      29       *               *     2 weeks